Aluminum Feeder Freight for a 200 Amp Service Lateral

Service-lateral freight: large aluminum conductors, short run, high weight per foot.

Formula SSC-2026.1

K method · SSC-2026.1

Minimum size

250 kcmil · 127.0 mm²

Single conductor set

Voltage drop

1.70 V

0.71% · end 238.3 V

Power loss

339 W

I²R at the operating current

Required ampacity

200.0 A

Each conductor 205 A

Material estimate

$1,173.50

3 conductors + RMC

Conductor weight

42.1 lb

19.1 kg · approximate insulated weight

Single-line and conductor gaugeLive scaled blueprint
MAIN PANELSingle-phase 240 VRMC · 50 ft · 250 kcmil · 127.0 mm²Aluminum lateral200 ASelected gauge250 kcmilcopper3/0 AWGDrop 0.71%End 238.3 VLoss 339 W

Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.

Bill of materials and shopping list
ItemNetWasteOrderUnit priceLine total
aluminum 250 kcmil · 127.0 mm²50 ft one waycuts excluded3 conductorsUSD$936.00
RMC conduit50 ft—50 ftUSD$237.50
Copper versus aluminum at this run
MaterialMinimum sizemm²DropEnd voltageLoss
aluminum250 kcmil · 127.0 mm²127.00.71%238.3 V339 W
copper3/0 AWG · 85.0 mm²85.00.64%238.5 V308 W
Same load at other one-way distances
DistanceMinimum sizeDropPercentEnd voltage
50 ft250 kcmil · 127.0 mm²1.70 V0.71%238.3 V
Show the deterministic formula

Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.

Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.

The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.

Engineering notes

The lateral is 200 A, 240 V, 50 ft, aluminum, in rigid conduit. Ampacity governs. The weight uses about one-third of the copper weight per foot for the same size, which is still a heavy coil at 250 kcmil and above. This is a planning weight for the order, not the utility's reel. Confirm 310.12 and the utility spec before you buy the lateral.

Code reference

NEC Table 310.16 and the serving utility specification. Dwelling service reductions in 310.12 are not applied automatically.

Field questions

Why is the run only 50 feet?
Service laterals are short, so the lesson is ampacity and coil weight, not a long-run voltage drop.
How is aluminum weight estimated?
The same-size copper weight is multiplied by 0.33. It is an allowance for the lighter metal, not a mill certificate.
What if two parallel sets are recommended?
The note will say so. Weight and cost both use the set count. Paralleling has its own NEC rules.