20 Amp Well Pump Wire Size at 150 Feet

A long 150 ft well branch where drop, not the 20 A breaker, picks the wire.

Formula SSC-2026.1

K method · SSC-2026.1

Minimum size

8 AWG · 8.37 mm²

Single conductor set

Voltage drop

4.69 V

1.95% · end 235.3 V

Power loss

94 W

I²R at the operating current

Required ampacity

20.0 A

Each conductor 50 A

Material estimate

$747.00

3 conductors + PVC

Conductor weight

28.8 lb

13.1 kg · approximate insulated weight

Single-line and conductor gaugeLive scaled blueprint
MAIN PANELSingle-phase 240 VPVC · 150 ft · 8 AWG · 8.37 mm²Well pump20 ASelected gauge8 AWGaluminum6 AWGDrop 1.95%End 235.3 VLoss 94 W

Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.

Bill of materials and shopping list
ItemNetWasteOrderUnit priceLine total
copper 8 AWG · 8.37 mm²150 ft one waycuts excluded3 conductorsUSD$604.50
PVC conduit150 ft—150 ftUSD$142.50
Copper versus aluminum at this run
MaterialMinimum sizemm²DropEnd voltageLoss
copper8 AWG · 8.37 mm²8.41.95%235.3 V94 W
aluminum6 AWG · 13.3 mm²13.32.02%235.2 V97 W
Same load at other one-way distances
DistanceMinimum sizeDropPercentEnd voltage
100 ft10 AWG · 5.26 mm²4.97 V2.07%235.0 V
150 ft8 AWG · 8.37 mm²4.69 V1.95%235.3 V
200 ft8 AWG · 8.37 mm²6.25 V2.60%233.7 V
300 ft6 AWG · 13.3 mm²5.90 V2.46%234.1 V
Show the deterministic formula

Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.

Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.

The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.

Engineering notes

Twenty amps at 240 V does not need a large conductor for ampacity. At 150 ft the 3 percent limit often does. The preset is copper in PVC, not continuous, because a well pump cycles. If the manufacturer lists a continuous or high-service-factor load, turn the 125 percent box on. Voltage drop at the pump reduces starting torque, so this is a case where meeting the percentage matters more than matching the breaker with the smallest legal wire.

Code reference

NEC 210.19(A) and 215.2(A) informational notes recommend 3 percent on a branch circuit and 5 percent total with the feeder. Ampacity follows the 75°C column of Table 310.16 plus the small-conductor limits. Confirm the adopted edition.

Field questions

Why is the wire larger than 12 AWG?
12 AWG copper is the usual 20 A conductor. Over 150 ft the drop calculation can require 10 or 8 AWG to stay inside 3 percent.
Should the pump be 120 or 240 volts?
This preset is 240 V. A 120 V pump at the same amps and distance has a much higher percent drop. Change the system control if the nameplate is 120 V.
Does PVC in a trench change resistance?
Not in this model. Conduit changes the cost. Temperature and bundling derating are called out as exclusions in the formula panel.