20 Amp Well Pump Wire Size at 150 Feet
A long 150 ft well branch where drop, not the 20 A breaker, picks the wire.
Formula SSC-2026.1
K method · SSC-2026.1
Minimum size
8 AWG · 8.37 mm²
Single conductor set
Voltage drop
4.69 V
1.95% · end 235.3 V
Power loss
94 W
I²R at the operating current
Required ampacity
20.0 A
Each conductor 50 A
Material estimate
$747.00
3 conductors + PVC
Conductor weight
28.8 lb
13.1 kg · approximate insulated weight
Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.
| Item | Net | Waste | Order | Unit price | Line total |
|---|---|---|---|---|---|
| copper 8 AWG · 8.37 mm² | 150 ft one way | cuts excluded | 3 conductors | USD | $604.50 |
| PVC conduit | 150 ft | — | 150 ft | USD | $142.50 |
| Material | Minimum size | mm² | Drop | End voltage | Loss |
|---|---|---|---|---|---|
| copper | 8 AWG · 8.37 mm² | 8.4 | 1.95% | 235.3 V | 94 W |
| aluminum | 6 AWG · 13.3 mm² | 13.3 | 2.02% | 235.2 V | 97 W |
| Distance | Minimum size | Drop | Percent | End voltage |
|---|---|---|---|---|
| 100 ft | 10 AWG · 5.26 mm² | 4.97 V | 2.07% | 235.0 V |
| 150 ft | 8 AWG · 8.37 mm² | 4.69 V | 1.95% | 235.3 V |
| 200 ft | 8 AWG · 8.37 mm² | 6.25 V | 2.60% | 233.7 V |
| 300 ft | 6 AWG · 13.3 mm² | 5.90 V | 2.46% | 234.1 V |
Show the deterministic formula
Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.
Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.
The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.
Contractor sign-off
Project: 20 Amp Well Pump Wire Size at 150 Feet
Prepared by
Date
Verified by (PE / electrician / inspector)
License number
Signature
This sheet is an estimate for ordering and layout discussion. It is not a sealed design. Confirm the quantities with a licensed local professional and the authority having jurisdiction before you buy or build.
Engineering notes
Twenty amps at 240 V does not need a large conductor for ampacity. At 150 ft the 3 percent limit often does. The preset is copper in PVC, not continuous, because a well pump cycles. If the manufacturer lists a continuous or high-service-factor load, turn the 125 percent box on. Voltage drop at the pump reduces starting torque, so this is a case where meeting the percentage matters more than matching the breaker with the smallest legal wire.
Code reference
NEC 210.19(A) and 215.2(A) informational notes recommend 3 percent on a branch circuit and 5 percent total with the feeder. Ampacity follows the 75°C column of Table 310.16 plus the small-conductor limits. Confirm the adopted edition.
Field questions
- Why is the wire larger than 12 AWG?
- 12 AWG copper is the usual 20 A conductor. Over 150 ft the drop calculation can require 10 or 8 AWG to stay inside 3 percent.
- Should the pump be 120 or 240 volts?
- This preset is 240 V. A 120 V pump at the same amps and distance has a much higher percent drop. Change the system control if the nameplate is 120 V.
- Does PVC in a trench change resistance?
- Not in this model. Conduit changes the cost. Temperature and bundling derating are called out as exclusions in the formula panel.