30 Amp RV Outlet Wire Gauge and Voltage Drop
A 120 V, 30 A TT-30 style outlet where voltage drop shows up quickly.
Formula SSC-2026.1
K method · SSC-2026.1
Minimum size
8 AWG · 8.37 mm²
Single conductor set
Voltage drop
3.52 V
2.93% · end 116.5 V
Power loss
105 W
I²R at the operating current
Required ampacity
30.0 A
Each conductor 50 A
Material estimate
$373.50
3 conductors + PVC
Conductor weight
14.4 lb
6.5 kg · approximate insulated weight
Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.
| Item | Net | Waste | Order | Unit price | Line total |
|---|---|---|---|---|---|
| copper 8 AWG · 8.37 mm² | 75 ft one way | cuts excluded | 3 conductors | USD | $302.25 |
| PVC conduit | 75 ft | — | 75 ft | USD | $71.25 |
| Material | Minimum size | mm² | Drop | End voltage | Loss |
|---|---|---|---|---|---|
| copper | 8 AWG · 8.37 mm² | 8.4 | 2.93% | 116.5 V | 105 W |
| aluminum | 4 AWG · 21.2 mm² | 21.2 | 1.90% | 117.7 V | 69 W |
| Distance | Minimum size | Drop | Percent | End voltage |
|---|---|---|---|---|
| 25 ft | 10 AWG · 5.26 mm² | 1.86 V | 1.55% | 118.1 V |
| 50 ft | 8 AWG · 8.37 mm² | 2.34 V | 1.95% | 117.7 V |
| 75 ft | 8 AWG · 8.37 mm² | 3.52 V | 2.93% | 116.5 V |
| 100 ft | 6 AWG · 13.3 mm² | 2.95 V | 2.46% | 117.1 V |
Show the deterministic formula
Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.
Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.
The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.
Contractor sign-off
Project: 30 Amp RV Outlet Wire Gauge and Voltage Drop
Prepared by
Date
Verified by (PE / electrician / inspector)
License number
Signature
This sheet is an estimate for ordering and layout discussion. It is not a sealed design. Confirm the quantities with a licensed local professional and the authority having jurisdiction before you buy or build.
Engineering notes
A 30 A RV receptacle on 120 V loses a larger share of its voltage than the same amps on 240 V. The preset is 75 ft of copper in PVC at a 3 percent limit, and the load is not marked continuous. Because the source is only 120 V, the calculator often leaves 10 AWG behind even though 10 AWG is the 30 A small-conductor limit. Confirm the pedestal breaker, the receptacle listing, and whether the site wants a 50 A 240 V outlet instead.
Code reference
NEC 210.19(A) and 215.2(A) informational notes recommend 3 percent on a branch circuit and 5 percent total with the feeder. Ampacity follows the 75°C column of Table 310.16 plus the small-conductor limits. Confirm the adopted edition.
Field questions
- Why does 120 volts need a larger wire than 240 volts?
- The same volt drop is a bigger percentage of 120 than of 240. Percent drop is Vdrop divided by the source voltage.
- Is 10 AWG always legal for a 30 amp RV outlet?
- 10 AWG copper meets the 30 A small-conductor rule, but it can miss a 3 percent drop on a long 120 V run. The result shows which limit governs.
- What conduit is assumed?
- PVC Schedule 40 at an editable price per foot. Changing to EMT or rigid metal changes the cost line, not the voltage-drop math.