240 V Mini-Split Heat Pump Wire Gauge
A 25 A heat pump on 240 V, 60 ft from the panel, with the 125 percent ampacity check on.
Formula SSC-2026.1
K method · SSC-2026.1
Minimum size
8 AWG · 8.37 mm²
Single conductor set
Voltage drop
2.34 V
0.98% · end 237.7 V
Power loss
59 W
I²R at the operating current
Required ampacity
31.3 A
Each conductor 50 A
Material estimate
$352.80
3 conductors + EMT
Conductor weight
11.5 lb
5.2 kg · approximate insulated weight
Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.
| Item | Net | Waste | Order | Unit price | Line total |
|---|---|---|---|---|---|
| copper 8 AWG · 8.37 mm² | 60 ft one way | cuts excluded | 3 conductors | USD | $241.80 |
| EMT conduit | 60 ft | — | 60 ft | USD | $111.00 |
| Material | Minimum size | mm² | Drop | End voltage | Loss |
|---|---|---|---|---|---|
| copper | 8 AWG · 8.37 mm² | 8.4 | 0.98% | 237.7 V | 59 W |
| aluminum | 8 AWG · 8.37 mm² | 8.4 | 1.61% | 236.1 V | 96 W |
| Distance | Minimum size | Drop | Percent | End voltage |
|---|---|---|---|---|
| 25 ft | 8 AWG · 8.37 mm² | 0.98 V | 0.41% | 239.0 V |
| 40 ft | 8 AWG · 8.37 mm² | 1.56 V | 0.65% | 238.4 V |
| 60 ft | 8 AWG · 8.37 mm² | 2.34 V | 0.98% | 237.7 V |
| 80 ft | 8 AWG · 8.37 mm² | 3.13 V | 1.30% | 236.9 V |
Show the deterministic formula
Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.
Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.
The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.
Contractor sign-off
Project: 240 V Mini-Split Heat Pump Wire Gauge
Prepared by
Date
Verified by (PE / electrician / inspector)
License number
Signature
This sheet is an estimate for ordering and layout discussion. It is not a sealed design. Confirm the quantities with a licensed local professional and the authority having jurisdiction before you buy or build.
Engineering notes
The operating current is 25 A and the continuous box is on, so the conductor must carry 31.25 A before voltage drop is considered. The run is 60 ft of copper in EMT at 3 percent. Use the MCA from the nameplate when you have it. The 25 A figure is a planning value for a small single-zone heat pump, not a substitute for the unit label. The disconnect and the whip are not in the conduit length.
Code reference
NEC 210.19(A) and 215.2(A) informational notes recommend 3 percent on a branch circuit and 5 percent total with the feeder. Ampacity follows the 75°C column of Table 310.16 plus the small-conductor limits. Confirm the adopted edition.
Field questions
- Should I use MCA or the breaker size?
- Ampacity follows the minimum circuit ampacity. The breaker follows the maximum overcurrent device on the nameplate. This page asks for the load current you want checked.
- Why mark a heat pump continuous?
- HVAC compressors can run for hours. The 125 percent factor keeps the conductor ahead of that duty. Turn it off only if a qualified person tells you the load is noncontinuous.
- What end voltage should I expect?
- End voltage is source voltage minus the drop. On 240 V, a 3 percent limit means you still have at least 232.8 V at the unit.