60 Amp Detached Garage Subpanel Wire Size

An 80 ft feeder to a detached garage subpanel at 60 A.

Formula SSC-2026.1

K method · SSC-2026.1

Minimum size

4 AWG · 21.2 mm²

Single conductor set

Voltage drop

4.88 V

2.03% · end 235.1 V

Power loss

293 W

I²R at the operating current

Required ampacity

60.0 A

Each conductor 65 A

Material estimate

$398.40

3 conductors + PVC

Conductor weight

12.3 lb

5.6 kg · approximate insulated weight

Single-line and conductor gaugeLive scaled blueprint
MAIN PANELSingle-phase 240 VPVC · 80 ft · 4 AWG · 21.2 mm²Garage subpanel60 ASelected gauge4 AWGcopper6 AWGDrop 2.03%End 235.1 VLoss 293 W

Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.

Bill of materials and shopping list
ItemNetWasteOrderUnit priceLine total
aluminum 4 AWG · 21.2 mm²80 ft one waycuts excluded3 conductorsUSD$322.40
PVC conduit80 ft—80 ftUSD$76.00
Copper versus aluminum at this run
MaterialMinimum sizemm²DropEnd voltageLoss
aluminum4 AWG · 21.2 mm²21.22.03%235.1 V293 W
copper6 AWG · 13.3 mm²13.31.97%235.3 V283 W
Same load at other one-way distances
DistanceMinimum sizeDropPercentEnd voltage
80 ft4 AWG · 21.2 mm²4.88 V2.03%235.1 V
Show the deterministic formula

Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.

Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.

The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.

Engineering notes

A detached garage feeder is 240 V, 60 A, 80 ft, with a 3 percent limit. The default conductor is aluminum in PVC because the trench is long enough for the cost difference to matter. The copper row is one click away in the comparison table. This does not calculate the separate equipment grounding conductor from Table 250.122, and it does not decide whether a grounding electrode is required at the garage.

Code reference

NEC 210.19(A) and 215.2(A) informational notes recommend 3 percent on a branch circuit and 5 percent total with the feeder. Ampacity follows the 75°C column of Table 310.16 plus the small-conductor limits. Confirm the adopted edition.

Field questions

Do I need four wires to a detached garage?
A feeder to an outbuilding is normally four conductors: two hots, a neutral, and an equipment ground, unless an older exception still applies locally. The cost line prices two hots plus a ground allowance and you should add the neutral if the subpanel needs it.
Why PVC instead of EMT?
PVC is the usual trench conduit. EMT is a thin-wall raceway for dry interior runs. The drop math does not change with the conduit type.
Is 60 amps enough for a garage?
That is a load calculation, not a voltage-drop result. Add the EV charger, compressor, and lights before you lock the feeder size.