50 Amp EV Charger Wire Size at 50, 75, and 100 Feet

A continuous 50 A, 240 V charger. The table repeats 50, 75, and 100 ft runs.

Formula SSC-2026.1

K method · SSC-2026.1

Minimum size

6 AWG · 13.3 mm²

Single conductor set

Voltage drop

3.69 V

1.54% · end 236.3 V

Power loss

184 W

I²R at the operating current

Required ampacity

62.5 A

Each conductor 65 A

Material estimate

$597.00

3 conductors + EMT

Conductor weight

22.1 lb

10.0 kg · approximate insulated weight

Single-line and conductor gaugeLive scaled blueprint
MAIN PANELSingle-phase 240 VEMT · 75 ft · 6 AWG · 13.3 mm²EV charger50 ASelected gauge6 AWGaluminum4 AWGDrop 1.54%End 236.3 VLoss 184 W

Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.

Bill of materials and shopping list
ItemNetWasteOrderUnit priceLine total
copper 6 AWG · 13.3 mm²75 ft one waycuts excluded3 conductorsUSD$458.25
EMT conduit75 ft—75 ftUSD$138.75
Copper versus aluminum at this run
MaterialMinimum sizemm²DropEnd voltageLoss
copper6 AWG · 13.3 mm²13.31.54%236.3 V184 W
aluminum4 AWG · 21.2 mm²21.21.59%236.2 V190 W
Same load at other one-way distances
DistanceMinimum sizeDropPercentEnd voltage
50 ft6 AWG · 13.3 mm²2.46 V1.02%237.5 V
75 ft6 AWG · 13.3 mm²3.69 V1.54%236.3 V
100 ft6 AWG · 13.3 mm²4.92 V2.05%235.1 V
Show the deterministic formula

Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.

Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.

The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.

Engineering notes

EV charging is treated as a continuous load, so ampacity is checked at 125 percent of 50 A, which is 62.5 A. Voltage drop is still calculated at 50 A. The default run is 75 ft of copper in EMT with a 3 percent limit. The distance table shows 50, 75, and 100 ft on the same load. A longer run can step the conductor up even when the breaker size stays at 50 or 60 A. Terminations must be listed for the conductor and the charger manual controls the breaker.

Code reference

NEC 210.19(A) and 215.2(A) informational notes recommend 3 percent on a branch circuit and 5 percent total with the feeder. Ampacity follows the 75°C column of Table 310.16 plus the small-conductor limits. Confirm the adopted edition.

Field questions

Why is a 50 amp charger not always 6 AWG?
Ampacity may allow 6 AWG copper at 75°C, but a long 240 V run can fail the 3 percent drop and step up. Read the distance table.
Does continuous mean the drop uses 62.5 amps?
No. The 125 percent factor is for ampacity. Voltage drop and watts lost use the 50 A operating current.
What if the charger is 100 feet from the panel?
Select the 100 ft row. If the percent turns amber or red, the recommended size has not met the limit you set.