200 Amp Main Service Entrance Wire Size

A 200 A service lateral where ampacity, not voltage drop, usually governs.

Formula SSC-2026.1

K method · SSC-2026.1

Minimum size

250 kcmil · 127.0 mm²

Single conductor set

Voltage drop

1.36 V

0.57% · end 238.6 V

Power loss

271 W

I²R at the operating current

Required ampacity

200.0 A

Each conductor 205 A

Material estimate

$938.80

3 conductors + RMC

Conductor weight

33.7 lb

15.3 kg · approximate insulated weight

Single-line and conductor gaugeLive scaled blueprint
MAIN PANELSingle-phase 240 VRMC · 40 ft · 250 kcmil · 127.0 mm²Service entrance200 ASelected gauge250 kcmilcopper3/0 AWGDrop 0.57%End 238.6 VLoss 271 W

Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.

Bill of materials and shopping list
ItemNetWasteOrderUnit priceLine total
aluminum 250 kcmil · 127.0 mm²40 ft one waycuts excluded3 conductorsUSD$748.80
RMC conduit40 ft—40 ftUSD$190.00
Copper versus aluminum at this run
MaterialMinimum sizemm²DropEnd voltageLoss
aluminum250 kcmil · 127.0 mm²127.00.57%238.6 V271 W
copper3/0 AWG · 85.0 mm²85.00.51%238.8 V246 W
Same load at other one-way distances
DistanceMinimum sizeDropPercentEnd voltage
40 ft250 kcmil · 127.0 mm²1.36 V0.57%238.6 V
Show the deterministic formula

Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.

Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.

The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.

Engineering notes

The preset is aluminum, 200 A, 240 V, 40 ft, in rigid metal conduit, with a 3 percent limit and the continuous box off. At this short distance the voltage drop is small, so the size is the smallest aluminum conductor at or above 200 A in the 75°C column. Dwelling services may use the NEC 310.12 sizing rule in editions that allow it, which can permit a smaller service conductor than the general table. The utility and the inspector control the service. Do not order lateral conductors from this page alone.

Code reference

NEC Table 310.16 75°C ampacity, the dwelling service provisions of 310.12 where adopted, and the serving utility's lateral specification. This estimate does not apply those exceptions automatically.

Field questions

Why is aluminum the default for 200 amps?
Service laterals are commonly aluminum because of weight and cost. Switch the conductor control to copper to see the smaller copper alternative and its price.
Will voltage drop change a 40 foot service?
Usually no. Read the drop percent. If it stays well under 3 percent, ampacity chose the size.
Does this include the ground rods or the mast?
No. The bill is conductor length plus conduit material. Bonding, the mast, and the meter socket are outside the calculation.