480 V Three-Phase 100 Amp Shop Feeder
A 100 A, 480 V, three-phase feeder, 120 ft, copper in EMT.
Formula SSC-2026.1
K method · SSC-2026.1
Minimum size
3 AWG · 26.7 mm²
Single conductor set
Voltage drop
5.10 V
1.06% · end 474.9 V
Power loss
883 W
I²R at the operating current
Required ampacity
100.0 A
Each conductor 100 A
Material estimate
$2,122.80
4 conductors + EMT
Conductor weight
93.6 lb
42.5 kg · approximate insulated weight
Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.
| Item | Net | Waste | Order | Unit price | Line total |
|---|---|---|---|---|---|
| copper 3 AWG · 26.7 mm² | 120 ft one way | cuts excluded | 4 conductors | USD | $1,900.80 |
| EMT conduit | 120 ft | — | 120 ft | USD | $222.00 |
| Material | Minimum size | mm² | Drop | End voltage | Loss |
|---|---|---|---|---|---|
| copper | 3 AWG · 26.7 mm² | 26.7 | 1.06% | 474.9 V | 883 W |
| aluminum | 1 AWG · 42.4 mm² | 42.4 | 1.10% | 474.7 V | 912 W |
| Distance | Minimum size | Drop | Percent | End voltage |
|---|---|---|---|---|
| 60 ft | 3 AWG · 26.7 mm² | 2.55 V | 0.53% | 477.5 V |
| 120 ft | 3 AWG · 26.7 mm² | 5.10 V | 1.06% | 474.9 V |
| 200 ft | 3 AWG · 26.7 mm² | 8.49 V | 1.77% | 471.5 V |
Show the deterministic formula
Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.
Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.
The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.
Contractor sign-off
Project: 480 V Three-Phase 100 Amp Shop Feeder
Prepared by
Date
Verified by (PE / electrician / inspector)
License number
Signature
This sheet is an estimate for ordering and layout discussion. It is not a sealed design. Confirm the quantities with a licensed local professional and the authority having jurisdiction before you buy or build.
Engineering notes
Three-phase drop uses 1.732 × K × I × D / cmil instead of the single-phase factor of 2. The higher source voltage makes the same volt drop a smaller percentage, so a 480 V feeder can stay smaller than a 240 V feeder of the same amps and length. The preset is 100 A, 120 ft, copper, 3 percent, not continuous. Power loss uses three conductors. Confirm the motor load, the starter, and any required equipment grounding conductor separately.
Code reference
NEC 210.19(A) and 215.2(A) informational notes recommend 3 percent on a branch circuit and 5 percent total with the feeder. Ampacity follows the 75°C column of Table 310.16 plus the small-conductor limits. Confirm the adopted edition.
Field questions
- Why is the three-phase factor 1.732?
- It is the square root of 3, used to convert the line current and conductor resistance into a line-to-line voltage drop.
- Does 480 volts always allow a smaller wire?
- Often, because percent drop divides by 480. Ampacity can still force a minimum size. Both checks are required.
- Can I switch this to 208 or 400 volts?
- Yes. The system control includes 208 V and 400 V three-phase. The same current and distance will show a larger percent drop at the lower voltage.