480 V Three-Phase 100 Amp Shop Feeder

A 100 A, 480 V, three-phase feeder, 120 ft, copper in EMT.

Formula SSC-2026.1

K method · SSC-2026.1

Minimum size

3 AWG · 26.7 mm²

Single conductor set

Voltage drop

5.10 V

1.06% · end 474.9 V

Power loss

883 W

I²R at the operating current

Required ampacity

100.0 A

Each conductor 100 A

Material estimate

$2,122.80

4 conductors + EMT

Conductor weight

93.6 lb

42.5 kg · approximate insulated weight

Single-line and conductor gaugeLive scaled blueprint
MAIN PANELThree-phase 480 VEMT · 120 ft · 3 AWG · 26.7 mm²Shop feeder100 ASelected gauge3 AWGaluminum1 AWGDrop 1.06%End 474.9 VLoss 883 W

Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.

Bill of materials and shopping list
ItemNetWasteOrderUnit priceLine total
copper 3 AWG · 26.7 mm²120 ft one waycuts excluded4 conductorsUSD$1,900.80
EMT conduit120 ft—120 ftUSD$222.00
Copper versus aluminum at this run
MaterialMinimum sizemm²DropEnd voltageLoss
copper3 AWG · 26.7 mm²26.71.06%474.9 V883 W
aluminum1 AWG · 42.4 mm²42.41.10%474.7 V912 W
Same load at other one-way distances
DistanceMinimum sizeDropPercentEnd voltage
60 ft3 AWG · 26.7 mm²2.55 V0.53%477.5 V
120 ft3 AWG · 26.7 mm²5.10 V1.06%474.9 V
200 ft3 AWG · 26.7 mm²8.49 V1.77%471.5 V
Show the deterministic formula

Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.

Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.

The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.

Engineering notes

Three-phase drop uses 1.732 × K × I × D / cmil instead of the single-phase factor of 2. The higher source voltage makes the same volt drop a smaller percentage, so a 480 V feeder can stay smaller than a 240 V feeder of the same amps and length. The preset is 100 A, 120 ft, copper, 3 percent, not continuous. Power loss uses three conductors. Confirm the motor load, the starter, and any required equipment grounding conductor separately.

Code reference

NEC 210.19(A) and 215.2(A) informational notes recommend 3 percent on a branch circuit and 5 percent total with the feeder. Ampacity follows the 75°C column of Table 310.16 plus the small-conductor limits. Confirm the adopted edition.

Field questions

Why is the three-phase factor 1.732?
It is the square root of 3, used to convert the line current and conductor resistance into a line-to-line voltage drop.
Does 480 volts always allow a smaller wire?
Often, because percent drop divides by 480. Ampacity can still force a minimum size. Both checks are required.
Can I switch this to 208 or 400 volts?
Yes. The system control includes 208 V and 400 V three-phase. The same current and distance will show a larger percent drop at the lower voltage.