20 amp copper run at 100 feet
Learn about the 3% voltage drop rule from the NEC for 240V copper branch circuits at 20A over 100 ft. Understand how derating does not apply in this context.
Formula SSC-2026.1
K method · SSC-2026.1
Minimum size
10 AWG · 5.26 mm²
Single conductor set
Voltage drop
4.97 V
2.07% · end 235.0 V
Power loss
99 W
I²R at the operating current
Required ampacity
20.0 A
Each conductor 30 A
Material estimate
$432.00
3 conductors + EMT
Conductor weight
11.1 lb
5.0 kg · approximate insulated weight
Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.
| Item | Net | Waste | Order | Unit price | Line total | Source Spec Material / Tool |
|---|---|---|---|---|---|---|
| copper 10 AWG · 5.26 mm² | 100 ft one way | cuts excluded | 3 conductors | USD | $247.00 | Source Spec Material / Tool |
| EMT conduit | 100 ft | — | 100 ft | USD | $185.00 | Source Spec Material / Tool |
| 20 A breaker | 2-pole | — | 1 | Match the calculated load | — | Source Spec Material / Tool |
Source links open a product search on the Amazon storefront for the selected currency. SiteSpecCalc may earn a commission. The link does not change the quantities above.
| Material | Minimum size | mm² | Drop | End voltage | Loss |
|---|---|---|---|---|---|
| copper | 10 AWG · 5.26 mm² | 5.3 | 2.07% | 235.0 V | 99 W |
| aluminum | 8 AWG · 8.37 mm² | 8.4 | 2.14% | 234.9 V | 103 W |
| Distance | Minimum size | Drop | Percent | End voltage |
|---|---|---|---|---|
| 100 ft | 10 AWG · 5.26 mm² | 4.97 V | 2.07% | 235.0 V |
| 125 ft | 10 AWG · 5.26 mm² | 6.21 V | 2.59% | 233.8 V |
Show the deterministic formula
Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.
Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.
The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.
Contractor sign-off
Project: 20 amp copper run at 100 feet
Prepared by
Date
Verified by (PE / electrician / inspector)
License number
Signature
This sheet is an estimate for ordering and layout discussion. It is not a sealed design. Confirm the quantities with a licensed local professional and the authority having jurisdiction before you buy or build.
Engineering notes
The National Electrical Code (NEC) provides guidelines for voltage drop in branch circuits to ensure efficient operation and safety. For a 240V copper branch circuit carrying 20A over a distance of 100 feet, the NEC recommends that the voltage drop should not exceed 3%. This means that the maximum allowable voltage drop would be 7.2 volts, ensuring that the voltage at the load remains within acceptable limits for optimal performance.
It is important to note that when calculating voltage drop for this scenario, derating factors for temperature, conduit fill, or other conditions are excluded. This means that the calculations are based solely on the conductor size and length, allowing for a straightforward assessment of whether the circuit meets the 3% guideline.
Code reference
Refer to NEC Article 210 for branch circuits and general voltage drop considerations.
Field questions
- What is the significance of the 3% voltage drop rule?
- The 3% voltage drop rule helps ensure that electrical devices operate efficiently and safely, preventing performance issues due to insufficient voltage at the load.
- Why is derating excluded when calculating voltage drop?
- Derating is excluded in this context to simplify calculations and focus on the conductor's ability to handle the specified current over the given distance without additional factors affecting performance.
- How do I calculate the voltage drop for my circuit?
- To calculate voltage drop, use the formula: Voltage Drop (V) = (2 x Length of Circuit (ft) x Current (A) x Resistance of Conductor (ohms/ft)). Ensure the result does not exceed 3% of the supply voltage.
- What happens if my voltage drop exceeds 3%?
- If the voltage drop exceeds 3%, it may lead to inefficient operation of electrical devices, potential overheating, and increased energy costs. It is advisable to adjust the conductor size or reduce the circuit length.
Explore Related Engineering Calculations
- 20 amp copper run at 40 feet
- 20 amp copper run at 60 feet
- 20 amp copper run at 80 feet
- 50 Amp EV Charger Wire Size at 50, 75, and 100 Feet
- 100 Amp Subpanel Feeder: Copper vs Aluminum
- 30 Amp RV Outlet Wire Gauge and Voltage Drop
- 14 by 12 ft slab at 8 inches
- Stair layout for a 42 inch rise
- 3/12 gable rafter on a 16 ft span
- 20ft gma pallet load