20 amp copper run at 60 feet
Learn about the 3% NEC informational note regarding voltage drop for 240V copper branch circuits at 20 A over 60 ft. Understand derating exclusions and ensure compliance with electrical codes.
Formula SSC-2026.1
K method · SSC-2026.1
Minimum size
12 AWG · 3.31 mm²
Single conductor set
Voltage drop
4.74 V
1.98% · end 235.3 V
Power loss
95 W
I²R at the operating current
Required ampacity
20.0 A
Each conductor 20 A
Material estimate
$207.72
3 conductors + EMT
Conductor weight
4.1 lb
1.9 kg · approximate insulated weight
Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.
| Item | Net | Waste | Order | Unit price | Line total | Source Spec Material / Tool |
|---|---|---|---|---|---|---|
| copper 12 AWG · 3.31 mm² | 60 ft one way | cuts excluded | 3 conductors | USD | $96.72 | Source Spec Material / Tool |
| EMT conduit | 60 ft | — | 60 ft | USD | $111.00 | Source Spec Material / Tool |
| 20 A breaker | 2-pole | — | 1 | Match the calculated load | — | Source Spec Material / Tool |
Source links open a product search on the Amazon storefront for the selected currency. SiteSpecCalc may earn a commission. The link does not change the quantities above.
| Material | Minimum size | mm² | Drop | End voltage | Loss |
|---|---|---|---|---|---|
| copper | 12 AWG · 3.31 mm² | 3.3 | 1.98% | 235.3 V | 95 W |
| aluminum | 10 AWG · 5.26 mm² | 5.3 | 2.04% | 235.1 V | 98 W |
| Distance | Minimum size | Drop | Percent | End voltage |
|---|---|---|---|---|
| 60 ft | 12 AWG · 3.31 mm² | 4.74 V | 1.98% | 235.3 V |
| 85 ft | 12 AWG · 3.31 mm² | 6.72 V | 2.80% | 233.3 V |
Show the deterministic formula
Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.
Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.
The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.
Contractor sign-off
Project: 20 amp copper run at 60 feet
Prepared by
Date
Verified by (PE / electrician / inspector)
License number
Signature
This sheet is an estimate for ordering and layout discussion. It is not a sealed design. Confirm the quantities with a licensed local professional and the authority having jurisdiction before you buy or build.
Engineering notes
The National Electrical Code (NEC) provides guidelines for voltage drop in branch circuits, recommending that the voltage drop should not exceed 3% for feeders and branch circuits. For a 240V copper branch circuit at 20 A over a distance of 60 ft, this means that the maximum allowable voltage drop is 7.2 volts (3% of 240V).
It's important to note that derating factors, which may apply to certain installations due to temperature or other conditions, are excluded from this specific calculation. This means that the 3% guideline is based solely on the length and load of the circuit without adjustments for derating.
Code reference
Refer to NEC Article 210 for branch circuits and NEC Article 215 for feeders regarding voltage drop considerations.
Field questions
- What is the significance of the 3% voltage drop rule?
- The 3% voltage drop rule is significant because it helps ensure that electrical devices receive adequate voltage for optimal performance and safety. Exceeding this drop can lead to inefficient operation and potential damage.
- Why is derating excluded from the 3% voltage drop calculation?
- Derating is excluded from the 3% voltage drop calculation to provide a clear guideline for standard circuit lengths and loads, ensuring that the basic performance of the circuit is maintained without additional complexity from environmental factors.
- How do I calculate the voltage drop for my circuit?
- To calculate the voltage drop, you can use the formula: Voltage Drop (V) = (2 * Length of Circuit (ft) * Current (A) * Resistance of Wire (ohms/ft)). For copper wire, you can find the resistance values in NEC tables.
- What happens if my voltage drop exceeds 3%?
- If your voltage drop exceeds 3%, it may lead to insufficient voltage at the load, potentially causing equipment malfunction or failure. It is advisable to adjust the wire size or reduce the length of the circuit to comply with the NEC recommendations.
Explore Related Engineering Calculations
- 20 amp copper run at 40 feet
- 20 amp copper run at 80 feet
- 20 amp copper run at 100 feet
- 50 Amp EV Charger Wire Size at 50, 75, and 100 Feet
- 100 Amp Subpanel Feeder: Copper vs Aluminum
- 30 Amp RV Outlet Wire Gauge and Voltage Drop
- 14 by 12 ft slab at 8 inches
- Stair layout for a 42 inch rise
- 3/12 gable rafter on a 16 ft span
- 20ft gma pallet load