20 amp copper run at 80 feet
Learn about the 3% NEC informational note regarding voltage drop for 240V copper branch circuits at 20A over 80 ft. Understand why derating is excluded in this context.
Formula SSC-2026.1
K method · SSC-2026.1
Minimum size
12 AWG · 3.31 mm²
Single conductor set
Voltage drop
6.32 V
2.63% · end 233.7 V
Power loss
126 W
I²R at the operating current
Required ampacity
20.0 A
Each conductor 20 A
Material estimate
$276.96
3 conductors + EMT
Conductor weight
5.5 lb
2.5 kg · approximate insulated weight
Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.
| Item | Net | Waste | Order | Unit price | Line total | Source Spec Material / Tool |
|---|---|---|---|---|---|---|
| copper 12 AWG · 3.31 mm² | 80 ft one way | cuts excluded | 3 conductors | USD | $128.96 | Source Spec Material / Tool |
| EMT conduit | 80 ft | — | 80 ft | USD | $148.00 | Source Spec Material / Tool |
| 20 A breaker | 2-pole | — | 1 | Match the calculated load | — | Source Spec Material / Tool |
Source links open a product search on the Amazon storefront for the selected currency. SiteSpecCalc may earn a commission. The link does not change the quantities above.
| Material | Minimum size | mm² | Drop | End voltage | Loss |
|---|---|---|---|---|---|
| copper | 12 AWG · 3.31 mm² | 3.3 | 2.63% | 233.7 V | 126 W |
| aluminum | 10 AWG · 5.26 mm² | 5.3 | 2.72% | 233.5 V | 131 W |
| Distance | Minimum size | Drop | Percent | End voltage |
|---|---|---|---|---|
| 80 ft | 12 AWG · 3.31 mm² | 6.32 V | 2.63% | 233.7 V |
| 105 ft | 10 AWG · 5.26 mm² | 5.22 V | 2.17% | 234.8 V |
Show the deterministic formula
Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.
Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.
The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.
Contractor sign-off
Project: 20 amp copper run at 80 feet
Prepared by
Date
Verified by (PE / electrician / inspector)
License number
Signature
This sheet is an estimate for ordering and layout discussion. It is not a sealed design. Confirm the quantities with a licensed local professional and the authority having jurisdiction before you buy or build.
Engineering notes
The National Electrical Code (NEC) provides guidelines to ensure safe and efficient electrical installations. One important aspect is the allowable voltage drop in branch circuits. For a 240V copper branch circuit carrying 20A over a distance of 80 feet, the NEC recommends a maximum voltage drop of 3% to maintain equipment performance and efficiency.
This 3% guideline is an informational note, meaning it serves as a recommendation rather than a strict requirement. It's important to note that derating of conductors due to temperature or other factors is excluded when calculating this voltage drop, as the focus is on maintaining voltage levels for optimal operation.
Code reference
National Electrical Code (NEC) - Article 210
Field questions
- What is the significance of the 3% voltage drop rule?
- The 3% voltage drop rule ensures that electrical equipment operates efficiently and reliably by maintaining adequate voltage levels throughout the circuit.
- Why is derating excluded when calculating voltage drop?
- Derating is excluded to simplify the voltage drop calculations and focus on maintaining voltage levels, rather than adjusting for temperature or other factors that could complicate the assessment.
- How do I calculate voltage drop for my circuit?
- To calculate voltage drop, you can use the formula: Voltage Drop (V) = (2 * Length of Circuit (ft) * Current (A) * Resistance of Conductor (Ω/ft)). Ensure to compare the result against the 3% guideline for your specific voltage.
Explore Related Engineering Calculations
- 20 amp copper run at 40 feet
- 20 amp copper run at 60 feet
- 20 amp copper run at 100 feet
- 50 Amp EV Charger Wire Size at 50, 75, and 100 Feet
- 100 Amp Subpanel Feeder: Copper vs Aluminum
- 30 Amp RV Outlet Wire Gauge and Voltage Drop
- 14 by 12 ft slab at 8 inches
- Stair layout for a 42 inch rise
- 3/12 gable rafter on a 16 ft span
- 20ft gma pallet load