20 amp copper run at 40 feet
Learn about the 3% NEC informational note regarding voltage drop for 240V copper branch circuits at 20A over 40 ft. Understand why derating is excluded in this context.
Formula SSC-2026.1
K method · SSC-2026.1
Minimum size
12 AWG · 3.31 mm²
Single conductor set
Voltage drop
3.16 V
1.32% · end 236.8 V
Power loss
63 W
I²R at the operating current
Required ampacity
20.0 A
Each conductor 20 A
Material estimate
$138.48
3 conductors + EMT
Conductor weight
2.8 lb
1.3 kg · approximate insulated weight
Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.
| Item | Net | Waste | Order | Unit price | Line total | Source Spec Material / Tool |
|---|---|---|---|---|---|---|
| copper 12 AWG · 3.31 mm² | 40 ft one way | cuts excluded | 3 conductors | USD | $64.48 | Source Spec Material / Tool |
| EMT conduit | 40 ft | — | 40 ft | USD | $74.00 | Source Spec Material / Tool |
| 20 A breaker | 2-pole | — | 1 | Match the calculated load | — | Source Spec Material / Tool |
Source links open a product search on the Amazon storefront for the selected currency. SiteSpecCalc may earn a commission. The link does not change the quantities above.
| Material | Minimum size | mm² | Drop | End voltage | Loss |
|---|---|---|---|---|---|
| copper | 12 AWG · 3.31 mm² | 3.3 | 1.32% | 236.8 V | 63 W |
| aluminum | 10 AWG · 5.26 mm² | 5.3 | 1.36% | 236.7 V | 65 W |
| Distance | Minimum size | Drop | Percent | End voltage |
|---|---|---|---|---|
| 40 ft | 12 AWG · 3.31 mm² | 3.16 V | 1.32% | 236.8 V |
| 65 ft | 12 AWG · 3.31 mm² | 5.14 V | 2.14% | 234.9 V |
Show the deterministic formula
Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.
Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.
The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.
Contractor sign-off
Project: 20 amp copper run at 40 feet
Prepared by
Date
Verified by (PE / electrician / inspector)
License number
Signature
This sheet is an estimate for ordering and layout discussion. It is not a sealed design. Confirm the quantities with a licensed local professional and the authority having jurisdiction before you buy or build.
Engineering notes
The National Electrical Code (NEC) provides guidelines to ensure safe and efficient electrical installations. One such guideline is the 3% voltage drop recommendation for branch circuits, which helps maintain electrical efficiency and equipment performance.
For a 240V copper branch circuit operating at 20A over a distance of 40 feet, the 3% voltage drop equates to a maximum allowable drop of 7.2V. This means that the voltage at the load should not fall below 232.8V to ensure optimal performance. It's important to note that derating factors, which may apply to other scenarios, are excluded when calculating the voltage drop for this specific case.
Code reference
Refer to NEC Article 210 for branch circuits and related voltage drop considerations.
Field questions
- What is the significance of the 3% voltage drop in electrical installations?
- The 3% voltage drop guideline helps ensure that electrical devices receive adequate voltage for optimal performance, reducing the risk of overheating and equipment failure.
- Why is derating excluded when calculating voltage drop for this circuit?
- Derating is excluded in this context because the 3% voltage drop guideline is a general recommendation for maintaining efficiency and does not account for additional factors that may apply in other scenarios.
- How do I calculate the voltage drop for my circuit?
- To calculate the voltage drop, you can use the formula: Voltage Drop (V) = (2 * Length of Circuit (ft) * Current (A) * Resistivity of Copper (Ω/ft)) / 1000. For a 240V circuit at 20A over 40 ft, ensure the drop does not exceed 7.2V.
Explore Related Engineering Calculations
- 20 amp copper run at 60 feet
- 20 amp copper run at 80 feet
- 20 amp copper run at 100 feet
- 50 Amp EV Charger Wire Size at 50, 75, and 100 Feet
- 100 Amp Subpanel Feeder: Copper vs Aluminum
- 30 Amp RV Outlet Wire Gauge and Voltage Drop
- 14 by 12 ft slab at 8 inches
- Stair layout for a 42 inch rise
- 3/12 gable rafter on a 16 ft span
- 20ft gma pallet load