Skip to content
SiteSpecCalc

Length imperial. Weight lb. Currency USD. Weight uses 1 lb = 0.45359237 kg. Currency converts US-dollar planning prices and does not change volumes, counts, or geometry.

100A Aluminum Subpanel Feeder at 150 Feet

Long aluminum feeders trade a larger size for a lower metal price. The comparison still offers the copper size at the same distance.

Formula SSC-2026.1

K method · SSC-2026.1

Minimum size

1/0 AWG · 53.5 mm²

Single conductor set

Voltage drop

6.02 V

2.51% · end 234.0 V

Power loss

602 W

I²R at the operating current

Required ampacity

100.0 A

Each conductor 120 A

Material estimate

$1,564.50

3 conductors + EMT

Conductor weight

54.9 lb

24.9 kg · approximate insulated weight

Single-line and conductor gaugeLive scaled blueprint
MAIN PANELSingle-phase 240 VEMT · 150 ft · 1/0 AWG · 53.5 mm²Aluminum subpanel100 ASelected gauge1/0 AWGcopper2 AWGDrop 2.51%End 234.0 VLoss 602 W

Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.

Bill of materials and shopping list
ItemNetWasteOrderUnit priceLine total
aluminum 1/0 AWG · 53.5 mm²150 ft one waycuts excluded3 conductorsUSD$1,287.00
EMT conduit150 ft—150 ftUSD$277.50
Copper versus aluminum at this run
MaterialMinimum sizemm²DropEnd voltageLoss
aluminum1/0 AWG · 53.5 mm²53.52.51%234.0 V602 W
copper2 AWG · 33.6 mm²33.62.43%234.2 V583 W
Same load at other one-way distances
DistanceMinimum sizeDropPercentEnd voltage
125 ft1 AWG · 42.4 mm²6.33 V2.64%233.7 V
150 ft1/0 AWG · 53.5 mm²6.02 V2.51%234.0 V
175 ft1/0 AWG · 53.5 mm²7.03 V2.93%233.0 V
Show the deterministic formula

Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.

Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.

The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.

Engineering notes

Long aluminum feeders trade a larger size for a lower metal price. The comparison still offers the copper size at the same distance. The run is 150 ft one way at 100 A on 1ph-240. K is 12.9 for copper and 21.2 for aluminum. Ambient temperature, bundling, and rooftop adders are not applied.

Code reference

NEC 210.19(A) and 215.2(A) informational notes recommend 3 percent on a branch circuit and 5 percent total with the feeder. Ampacity follows the 75°C column of Table 310.16 plus the small-conductor limits. Confirm the adopted edition.

Field questions

What current is used for the 100 A voltage drop?
Both the drop and the ampacity check use the entered amps, because this preset is not marked continuous.
Does this replace the equipment installation manual?
No. The nameplate, the breaker, and the adopted NEC edition still control. This page is the K-method size and the percent drop.
Can I switch copper and aluminum?
Yes. The conductor control and the comparison table both recompute size, drop, and the planning cost.

Explore Related Engineering Calculations