125A Feeder Wire Size at 60 Feet

A 125 A feeder at 60 ft sits between a 100 A subpanel and a 150 A feeder. The page uses the 5 percent feeder planning limit.

Formula SSC-2026.1

K method · SSC-2026.1

Minimum size

1 AWG · 42.4 mm²

Single conductor set

Voltage drop

2.31 V

0.96% · end 237.7 V

Power loss

289 W

I²R at the operating current

Required ampacity

125.0 A

Each conductor 130 A

Material estimate

$1,171.80

3 conductors + EMT

Conductor weight

54.0 lb

24.5 kg · approximate insulated weight

Single-line and conductor gaugeLive scaled blueprint
MAIN PANELSingle-phase 240 VEMT · 60 ft · 1 AWG · 42.4 mm²125A feeder125 ASelected gauge1 AWGaluminum2/0 AWGDrop 0.96%End 237.7 VLoss 289 W

Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.

Bill of materials and shopping list
ItemNetWasteOrderUnit priceLine total
copper 1 AWG · 42.4 mm²60 ft one waycuts excluded3 conductorsUSD$1,060.80
EMT conduit60 ft—60 ftUSD$111.00
Copper versus aluminum at this run
MaterialMinimum sizemm²DropEnd voltageLoss
copper1 AWG · 42.4 mm²42.40.96%237.7 V289 W
aluminum2/0 AWG · 67.4 mm²67.41.00%237.6 V299 W
Same load at other one-way distances
DistanceMinimum sizeDropPercentEnd voltage
35 ft1 AWG · 42.4 mm²1.35 V0.56%238.7 V
60 ft1 AWG · 42.4 mm²2.31 V0.96%237.7 V
85 ft1 AWG · 42.4 mm²3.28 V1.36%236.7 V
Show the deterministic formula

Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.

Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.

The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.

Engineering notes

A 125 A feeder at 60 ft sits between a 100 A subpanel and a 150 A feeder. The page uses the 5 percent feeder planning limit. The run is 60 ft one way at 125 A on 1ph-240. K is 12.9 for copper and 21.2 for aluminum. Ambient temperature, bundling, and rooftop adders are not applied.

Code reference

NEC 210.19(A) and 215.2(A) informational notes recommend 3 percent on a branch circuit and 5 percent total with the feeder. Ampacity follows the 75°C column of Table 310.16 plus the small-conductor limits. Confirm the adopted edition.

Field questions

What current is used for the 125 A voltage drop?
Both the drop and the ampacity check use the entered amps, because this preset is not marked continuous.
Does this replace the equipment installation manual?
No. The nameplate, the breaker, and the adopted NEC edition still control. This page is the K-method size and the percent drop.
Can I switch copper and aluminum?
Yes. The conductor control and the comparison table both recompute size, drop, and the planning cost.