150A Feeder Wire Size at 80 Feet
A 150 A feeder uses the 5 percent feeder planning limit on this page. It is not a service calculation and it does not apply the dwelling 310.12 exception.
Formula SSC-2026.1
K method · SSC-2026.1
Minimum size
1/0 AWG · 53.5 mm²
Single conductor set
Voltage drop
2.93 V
1.22% · end 237.1 V
Power loss
440 W
I²R at the operating current
Required ampacity
150.0 A
Each conductor 150 A
Material estimate
$1,895.20
3 conductors + EMT
Conductor weight
88.8 lb
40.3 kg · approximate insulated weight
Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.
| Item | Net | Waste | Order | Unit price | Line total |
|---|---|---|---|---|---|
| copper 1/0 AWG · 53.5 mm² | 80 ft one way | cuts excluded | 3 conductors | USD | $1,747.20 |
| EMT conduit | 80 ft | — | 80 ft | USD | $148.00 |
| Material | Minimum size | mm² | Drop | End voltage | Loss |
|---|---|---|---|---|---|
| copper | 1/0 AWG · 53.5 mm² | 53.5 | 1.22% | 237.1 V | 440 W |
| aluminum | 3/0 AWG · 85.0 mm² | 85.0 | 1.26% | 237.0 V | 455 W |
| Distance | Minimum size | Drop | Percent | End voltage |
|---|---|---|---|---|
| 55 ft | 1/0 AWG · 53.5 mm² | 2.02 V | 0.84% | 238.0 V |
| 80 ft | 1/0 AWG · 53.5 mm² | 2.93 V | 1.22% | 237.1 V |
| 105 ft | 1/0 AWG · 53.5 mm² | 3.85 V | 1.60% | 236.2 V |
Show the deterministic formula
Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.
Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.
The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.
Contractor sign-off
Project: 150A Feeder Wire Size at 80 Feet
Prepared by
Date
Verified by (PE / electrician / inspector)
License number
Signature
This sheet is an estimate for ordering and layout discussion. It is not a sealed design. Confirm the quantities with a licensed local professional and the authority having jurisdiction before you buy or build.
Engineering notes
A 150 A feeder uses the 5 percent feeder planning limit on this page. It is not a service calculation and it does not apply the dwelling 310.12 exception. The run is 80 ft one way at 150 A on 1ph-240. K is 12.9 for copper and 21.2 for aluminum. Ambient temperature, bundling, and rooftop adders are not applied.
Code reference
NEC 210.19(A) and 215.2(A) informational notes recommend 3 percent on a branch circuit and 5 percent total with the feeder. Ampacity follows the 75°C column of Table 310.16 plus the small-conductor limits. Confirm the adopted edition.
Field questions
- What current is used for the 150 A voltage drop?
- Both the drop and the ampacity check use the entered amps, because this preset is not marked continuous.
- Does this replace the equipment installation manual?
- No. The nameplate, the breaker, and the adopted NEC edition still control. This page is the K-method size and the percent drop.
- Can I switch copper and aluminum?
- Yes. The conductor control and the comparison table both recompute size, drop, and the planning cost.
Explore Related Engineering Calculations
- 50 Amp EV Charger Wire Size at 50, 75, and 100 Feet
- 100 Amp Subpanel Feeder: Copper vs Aluminum
- 30 Amp RV Outlet Wire Gauge and Voltage Drop
- 200 Amp Main Service Entrance Wire Size
- 240 V Mini-Split Heat Pump Wire Gauge
- 60 Amp Detached Garage Subpanel Wire Size
- 20×20 Garage Slab: 4 Inch vs 6 Inch
- Deck Stair Stringer Calculator, 36 to 96 Inch Rise
- 6/12 Roof Pitch, Rafter Length, and Shingle Bundles
- 20 ft dry, US 48×40 pallets: Pallet Count, CBM, and Payload