20 amp copper run at 150 feet

Learn about the 3% voltage drop rule in the NEC for 240V copper branch circuits at 20A over 150 ft, and understand why derating is excluded.

Formula SSC-2026.1

K method · SSC-2026.1

Minimum size

8 AWG · 8.37 mm²

Single conductor set

Voltage drop

4.69 V

1.95% · end 235.3 V

Power loss

94 W

I²R at the operating current

Required ampacity

20.0 A

Each conductor 50 A

Material estimate

$882.00

3 conductors + EMT

Conductor weight

28.8 lb

13.1 kg · approximate insulated weight

Single-line and conductor gaugeLive scaled blueprint
MAIN PANELSingle-phase 240 VEMT · 150 ft · 8 AWG · 8.37 mm²Branch circuit20 ASelected gauge8 AWGaluminum6 AWGDrop 1.95%End 235.3 VLoss 94 W

Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.

Bill of materials and shopping list
ItemNetWasteOrderUnit priceLine totalSource Spec Material / Tool
copper 8 AWG · 8.37 mm²150 ft one waycuts excluded3 conductorsUSD$604.50Source Spec Material / Tool
EMT conduit150 ft—150 ftUSD$277.50Source Spec Material / Tool
20 A breaker2-pole—1Match the calculated load—Source Spec Material / Tool

Source links open a product search on the Amazon storefront for the selected currency. SiteSpecCalc may earn a commission. The link does not change the quantities above.

Copper versus aluminum at this run
MaterialMinimum sizemm²DropEnd voltageLoss
copper8 AWG · 8.37 mm²8.41.95%235.3 V94 W
aluminum6 AWG · 13.3 mm²13.32.02%235.2 V97 W
Same load at other one-way distances
DistanceMinimum sizeDropPercentEnd voltage
150 ft8 AWG · 8.37 mm²4.69 V1.95%235.3 V
175 ft8 AWG · 8.37 mm²5.47 V2.28%234.5 V
Show the deterministic formula

Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.

Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.

The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.

Engineering notes

The National Electrical Code (NEC) recommends a maximum voltage drop of 3% for branch circuits to ensure efficient operation of electrical equipment. For a 240V copper branch circuit at 20A over a distance of 150 ft, this means that the voltage drop should not exceed 7.2 volts (3% of 240V). This guideline helps maintain performance and safety in electrical installations.

It's important to note that derating due to ambient temperature or other factors is not considered in this calculation. The 3% rule is strictly about maintaining voltage levels to prevent equipment malfunction and ensure energy efficiency.

Code reference

Refer to NEC Article 210.19(A)(1) for branch circuits and the informational note regarding voltage drop.

Field questions

What is the significance of the 3% voltage drop rule?
The 3% voltage drop rule helps ensure that electrical equipment operates efficiently and safely, preventing performance issues due to insufficient voltage.
Why is derating excluded from the 3% voltage drop calculation?
Derating is excluded because the 3% voltage drop rule specifically addresses the maximum allowable drop for efficient operation, independent of other factors like temperature or conduit fill.
How do I calculate the voltage drop for my circuit?
To calculate voltage drop, you can use the formula: Voltage Drop (V) = (2 * Length of Circuit (ft) * Current (A) * Resistance of Wire (Ω/ft)). For copper wire, refer to standard resistance values based on wire gauge.