30 amp copper run at 60 feet

Learn about the 3% NEC informational note regarding voltage drop for 240V copper branch circuits at 30A over 60 ft. Understand derating exclusions and compliance.

Formula SSC-2026.1

K method · SSC-2026.1

Minimum size

10 AWG · 5.26 mm²

Single conductor set

Voltage drop

4.47 V

1.86% · end 235.5 V

Power loss

134 W

I²R at the operating current

Required ampacity

30.0 A

Each conductor 30 A

Material estimate

$259.20

3 conductors + EMT

Conductor weight

6.7 lb

3.0 kg · approximate insulated weight

Single-line and conductor gaugeLive scaled blueprint
MAIN PANELSingle-phase 240 VEMT · 60 ft · 10 AWG · 5.26 mm²Branch circuit30 ASelected gauge10 AWGaluminum8 AWGDrop 1.86%End 235.5 VLoss 134 W

Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.

Bill of materials and shopping list
ItemNetWasteOrderUnit priceLine totalSource Spec Material / Tool
copper 10 AWG · 5.26 mm²60 ft one waycuts excluded3 conductorsUSD$148.20Source Spec Material / Tool
EMT conduit60 ft—60 ftUSD$111.00Source Spec Material / Tool
30 A breaker2-pole—1Match the calculated load—Source Spec Material / Tool

Source links open a product search on the Amazon storefront for the selected currency. SiteSpecCalc may earn a commission. The link does not change the quantities above.

Copper versus aluminum at this run
MaterialMinimum sizemm²DropEnd voltageLoss
copper10 AWG · 5.26 mm²5.31.86%235.5 V134 W
aluminum8 AWG · 8.37 mm²8.41.93%235.4 V139 W
Same load at other one-way distances
DistanceMinimum sizeDropPercentEnd voltage
60 ft10 AWG · 5.26 mm²4.47 V1.86%235.5 V
85 ft10 AWG · 5.26 mm²6.34 V2.64%233.7 V
Show the deterministic formula

Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.

Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.

The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.

Engineering notes

The National Electrical Code (NEC) provides guidelines to ensure safe and efficient electrical installations. One key aspect is the voltage drop in branch circuits. For a 240V copper branch circuit carrying 30A over a distance of 60 feet, the NEC recommends that the voltage drop should not exceed 3% of the supply voltage. This translates to a maximum allowable drop of 7.2 volts, ensuring that the equipment receives sufficient voltage for optimal performance.

It's important to note that derating factors, which may apply in certain conditions, are excluded from this calculation. This means that the 3% guideline stands independently, focusing solely on the voltage drop due to distance and load without additional adjustments for temperature or other environmental factors.

Code reference

Refer to NEC Article 210 for branch circuits and NEC Article 310 for conductors.

Field questions

What is the significance of the 3% voltage drop guideline?
The 3% voltage drop guideline helps ensure that electrical equipment operates efficiently and safely, preventing performance issues due to insufficient voltage.
Are there any exceptions to the 3% rule?
While the 3% guideline is a standard recommendation, specific applications may have different requirements. Always consult local codes and regulations.
What does it mean that derating is excluded?
Excluding derating means that the 3% voltage drop calculation is based solely on the distance and load without considering additional factors like temperature or conductor bundling.
How do I calculate the voltage drop for my circuit?
To calculate voltage drop, you can use the formula: Voltage Drop (V) = 2 × Length (ft) × Current (A) × Resistance (Ω/ft). For copper conductors, refer to NEC tables for resistance values.

Explore Related Engineering Calculations