48A Heat Pump Wire Size at 90 Feet

Treat a 48 A heat-pump nameplate as continuous for ampacity unless the equipment instructions say otherwise. Drop uses 48 A.

Formula SSC-2026.1

K method · SSC-2026.1

Minimum size

6 AWG · 13.3 mm²

Single conductor set

Voltage drop

4.25 V

1.77% · end 235.8 V

Power loss

204 W

I²R at the operating current

Required ampacity

60.0 A

Each conductor 65 A

Material estimate

$716.40

3 conductors + EMT

Conductor weight

26.5 lb

12.0 kg · approximate insulated weight

Single-line and conductor gaugeLive scaled blueprint
MAIN PANELSingle-phase 240 VEMT · 90 ft · 6 AWG · 13.3 mm²Heat pump48 ASelected gauge6 AWGaluminum4 AWGDrop 1.77%End 235.8 VLoss 204 W

Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.

Bill of materials and shopping list
ItemNetWasteOrderUnit priceLine total
copper 6 AWG · 13.3 mm²90 ft one waycuts excluded3 conductorsUSD$549.90
EMT conduit90 ft—90 ftUSD$166.50
Copper versus aluminum at this run
MaterialMinimum sizemm²DropEnd voltageLoss
copper6 AWG · 13.3 mm²13.31.77%235.8 V204 W
aluminum4 AWG · 21.2 mm²21.21.83%235.6 V211 W
Same load at other one-way distances
DistanceMinimum sizeDropPercentEnd voltage
65 ft6 AWG · 13.3 mm²3.07 V1.28%236.9 V
90 ft6 AWG · 13.3 mm²4.25 V1.77%235.8 V
115 ft6 AWG · 13.3 mm²5.43 V2.26%234.6 V
Show the deterministic formula

Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.

Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.

The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.

Engineering notes

Treat a 48 A heat-pump nameplate as continuous for ampacity unless the equipment instructions say otherwise. Drop uses 48 A. The run is 90 ft one way at 48 A on 1ph-240. K is 12.9 for copper and 21.2 for aluminum. Ambient temperature, bundling, and rooftop adders are not applied.

Code reference

NEC 210.19(A) and 215.2(A) informational notes recommend 3 percent on a branch circuit and 5 percent total with the feeder. Ampacity follows the 75°C column of Table 310.16 plus the small-conductor limits. Confirm the adopted edition.

Field questions

What current is used for the 48 A voltage drop?
Voltage drop uses the operating amps. Ampacity uses 125 percent because the load is marked continuous.
Does this replace the equipment installation manual?
No. The nameplate, the breaker, and the adopted NEC edition still control. This page is the K-method size and the percent drop.
Can I switch copper and aluminum?
Yes. The conductor control and the comparison table both recompute size, drop, and the planning cost.