80A Garage Feeder, Aluminum, 120 Feet

An 80 A aluminum feeder at 120 ft is a detached-garage planning run. Conduit fill and burial depth are not calculated.

Formula SSC-2026.1

K method · SSC-2026.1

Minimum size

2 AWG · 33.6 mm²

Single conductor set

Voltage drop

6.13 V

2.56% · end 233.9 V

Power loss

491 W

I²R at the operating current

Required ampacity

80.0 A

Each conductor 90 A

Material estimate

$908.40

3 conductors + EMT

Conductor weight

27.9 lb

12.7 kg · approximate insulated weight

Single-line and conductor gaugeLive scaled blueprint
MAIN PANELSingle-phase 240 VEMT · 120 ft · 2 AWG · 33.6 mm²Garage feeder80 ASelected gauge2 AWGcopper4 AWGDrop 2.56%End 233.9 VLoss 491 W

Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.

Bill of materials and shopping list
ItemNetWasteOrderUnit priceLine total
aluminum 2 AWG · 33.6 mm²120 ft one waycuts excluded3 conductorsUSD$686.40
EMT conduit120 ft—120 ftUSD$222.00
Copper versus aluminum at this run
MaterialMinimum sizemm²DropEnd voltageLoss
aluminum2 AWG · 33.6 mm²33.62.56%233.9 V491 W
copper4 AWG · 21.2 mm²21.22.47%234.1 V475 W
Same load at other one-way distances
DistanceMinimum sizeDropPercentEnd voltage
95 ft2 AWG · 33.6 mm²4.86 V2.02%235.1 V
120 ft2 AWG · 33.6 mm²6.13 V2.56%233.9 V
145 ft1 AWG · 42.4 mm²5.88 V2.45%234.1 V
Show the deterministic formula

Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.

Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.

The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.

Engineering notes

An 80 A aluminum feeder at 120 ft is a detached-garage planning run. Conduit fill and burial depth are not calculated. The run is 120 ft one way at 80 A on 1ph-240. K is 12.9 for copper and 21.2 for aluminum. Ambient temperature, bundling, and rooftop adders are not applied.

Code reference

NEC 210.19(A) and 215.2(A) informational notes recommend 3 percent on a branch circuit and 5 percent total with the feeder. Ampacity follows the 75°C column of Table 310.16 plus the small-conductor limits. Confirm the adopted edition.

Field questions

What current is used for the 80 A voltage drop?
Both the drop and the ampacity check use the entered amps, because this preset is not marked continuous.
Does this replace the equipment installation manual?
No. The nameplate, the breaker, and the adopted NEC edition still control. This page is the K-method size and the percent drop.
Can I switch copper and aluminum?
Yes. The conductor control and the comparison table both recompute size, drop, and the planning cost.