30 amp copper run at 100 feet

Learn about the 3% NEC informational note for 240V copper branch circuits at 30A over 100 ft. Understand derating exclusions and ensure code compliance.

Formula SSC-2026.1

K method · SSC-2026.1

Minimum size

8 AWG · 8.37 mm²

Single conductor set

Voltage drop

4.69 V

1.95% · end 235.3 V

Power loss

141 W

I²R at the operating current

Required ampacity

30.0 A

Each conductor 50 A

Material estimate

$588.00

3 conductors + EMT

Conductor weight

19.2 lb

8.7 kg · approximate insulated weight

Single-line and conductor gaugeLive scaled blueprint
MAIN PANELSingle-phase 240 VEMT · 100 ft · 8 AWG · 8.37 mm²Branch circuit30 ASelected gauge8 AWGaluminum6 AWGDrop 1.95%End 235.3 VLoss 141 W

Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.

Bill of materials and shopping list
ItemNetWasteOrderUnit priceLine totalSource Spec Material / Tool
copper 8 AWG · 8.37 mm²100 ft one waycuts excluded3 conductorsUSD$403.00Source Spec Material / Tool
EMT conduit100 ft—100 ftUSD$185.00Source Spec Material / Tool
30 A breaker2-pole—1Match the calculated load—Source Spec Material / Tool

Source links open a product search on the Amazon storefront for the selected currency. SiteSpecCalc may earn a commission. The link does not change the quantities above.

Copper versus aluminum at this run
MaterialMinimum sizemm²DropEnd voltageLoss
copper8 AWG · 8.37 mm²8.41.95%235.3 V141 W
aluminum6 AWG · 13.3 mm²13.32.02%235.2 V145 W
Same load at other one-way distances
DistanceMinimum sizeDropPercentEnd voltage
100 ft8 AWG · 8.37 mm²4.69 V1.95%235.3 V
125 ft8 AWG · 8.37 mm²5.86 V2.44%234.1 V
Show the deterministic formula

Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.

Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.

The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.

Engineering notes

The National Electrical Code (NEC) provides guidelines to ensure safe and efficient electrical installations. For a 240V copper branch circuit operating at 30A over a distance of 100 feet, the 3% voltage drop rule is an important consideration. This rule suggests that the voltage drop should not exceed 3% of the supply voltage to maintain efficiency and performance.

In this case, a 3% voltage drop would equate to 7.2 volts (0.03 x 240V), meaning the voltage at the load should not fall below 232.8 volts. It's also crucial to note that derating for conductor ampacity due to ambient temperature or other factors is excluded when calculating this voltage drop, ensuring that the circuit remains compliant with NEC standards.

Code reference

Refer to NEC Article 310 for conductor ampacity and Article 215 for branch circuits.

Field questions

What is the significance of the 3% voltage drop rule?
The 3% voltage drop rule is significant as it helps ensure that electrical devices receive adequate voltage for optimal performance, reducing the risk of overheating and equipment failure.
Why is derating excluded from the 3% voltage drop calculation?
Derating is excluded from the voltage drop calculation to provide a clear guideline for maintaining efficiency without complicating the assessment with additional factors that may affect conductor performance.
How do I calculate the voltage drop for my circuit?
To calculate voltage drop, you can use the formula: Voltage Drop (V) = (2 x Length of Circuit (ft) x Current (A) x Resistance of Conductor (ohms/ft)). Ensure you use the appropriate resistance value for copper conductors.

Explore Related Engineering Calculations