40 amp copper run at 100 feet

Learn about the 3% NEC informational note regarding voltage drop for 240V copper branch circuits at 40A over 100 ft. Understand derating exclusions and ensure compliance.

Formula SSC-2026.1

K method · SSC-2026.1

Minimum size

8 AWG · 8.37 mm²

Single conductor set

Voltage drop

6.25 V

2.60% · end 233.7 V

Power loss

250 W

I²R at the operating current

Required ampacity

40.0 A

Each conductor 50 A

Material estimate

$588.00

3 conductors + EMT

Conductor weight

19.2 lb

8.7 kg · approximate insulated weight

Single-line and conductor gaugeLive scaled blueprint
MAIN PANELSingle-phase 240 VEMT · 100 ft · 8 AWG · 8.37 mm²Branch circuit40 ASelected gauge8 AWGaluminum6 AWGDrop 2.60%End 233.7 VLoss 250 W

Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.

Bill of materials and shopping list
ItemNetWasteOrderUnit priceLine totalSource Spec Material / Tool
copper 8 AWG · 8.37 mm²100 ft one waycuts excluded3 conductorsUSD$403.00Source Spec Material / Tool
EMT conduit100 ft—100 ftUSD$185.00Source Spec Material / Tool
40 A breaker2-pole—1Match the calculated load—Source Spec Material / Tool

Source links open a product search on the Amazon storefront for the selected currency. SiteSpecCalc may earn a commission. The link does not change the quantities above.

Copper versus aluminum at this run
MaterialMinimum sizemm²DropEnd voltageLoss
copper8 AWG · 8.37 mm²8.42.60%233.7 V250 W
aluminum6 AWG · 13.3 mm²13.32.69%233.5 V259 W
Same load at other one-way distances
DistanceMinimum sizeDropPercentEnd voltage
100 ft8 AWG · 8.37 mm²6.25 V2.60%233.7 V
125 ft6 AWG · 13.3 mm²4.92 V2.05%235.1 V
Show the deterministic formula

Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.

Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.

The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.

Engineering notes

The National Electrical Code (NEC) provides guidelines for voltage drop in branch circuits to ensure efficient operation and safety. For a 240V copper branch circuit carrying 40A over a distance of 100 ft, the 3% voltage drop guideline suggests that the maximum allowable voltage drop should not exceed 7.2 volts (3% of 240V). This is crucial for maintaining the performance of electrical equipment and preventing overheating.

It's important to note that derating factors for conductors, such as temperature or conduit fill, do not apply to the calculation of voltage drop in this context. The focus remains solely on the distance and load to ensure compliance with the NEC's recommendations.

Code reference

Refer to NEC Article 310 for conductor ampacity and voltage drop considerations.

Field questions

What is the significance of the 3% voltage drop guideline?
The 3% voltage drop guideline helps ensure that electrical devices operate efficiently and safely, preventing issues like overheating and reduced performance.
Why is derating excluded from voltage drop calculations?
Derating factors are excluded from voltage drop calculations to provide a clear and straightforward assessment of voltage drop based solely on distance and load, ensuring compliance with NEC guidelines.
How do I calculate the voltage drop for my circuit?
To calculate voltage drop, use the formula: Voltage Drop (V) = (2 × Length of Circuit (ft) × Current (A) × Resistance of Conductor (Ω/ft)). Ensure the result does not exceed the allowable drop based on the 3% guideline.

Explore Related Engineering Calculations