40 amp copper run at 150 feet

Learn about the 3% NEC informational note regarding voltage drop for 240V copper branch circuits at 40A over 150 ft. Understand derating exclusions and ensure compliance.

Formula SSC-2026.1

K method · SSC-2026.1

Minimum size

6 AWG · 13.3 mm²

Single conductor set

Voltage drop

5.90 V

2.46% · end 234.1 V

Power loss

236 W

I²R at the operating current

Required ampacity

40.0 A

Each conductor 65 A

Material estimate

$1,194.00

3 conductors + EMT

Conductor weight

44.1 lb

20.0 kg · approximate insulated weight

Single-line and conductor gaugeLive scaled blueprint
MAIN PANELSingle-phase 240 VEMT · 150 ft · 6 AWG · 13.3 mm²Branch circuit40 ASelected gauge6 AWGaluminum4 AWGDrop 2.46%End 234.1 VLoss 236 W

Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.

Bill of materials and shopping list
ItemNetWasteOrderUnit priceLine totalSource Spec Material / Tool
copper 6 AWG · 13.3 mm²150 ft one waycuts excluded3 conductorsUSD$916.50Source Spec Material / Tool
EMT conduit150 ft—150 ftUSD$277.50Source Spec Material / Tool
40 A breaker2-pole—1Match the calculated load—Source Spec Material / Tool

Source links open a product search on the Amazon storefront for the selected currency. SiteSpecCalc may earn a commission. The link does not change the quantities above.

Copper versus aluminum at this run
MaterialMinimum sizemm²DropEnd voltageLoss
copper6 AWG · 13.3 mm²13.32.46%234.1 V236 W
aluminum4 AWG · 21.2 mm²21.22.54%233.9 V244 W
Same load at other one-way distances
DistanceMinimum sizeDropPercentEnd voltage
150 ft6 AWG · 13.3 mm²5.90 V2.46%234.1 V
175 ft6 AWG · 13.3 mm²6.88 V2.87%233.1 V
Show the deterministic formula

Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.

Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.

The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.

Engineering notes

The National Electrical Code (NEC) provides guidelines for voltage drop in branch circuits to ensure efficient operation and safety. For a 240V copper branch circuit carrying 40A over a distance of 150 ft, the 3% voltage drop rule suggests that the maximum allowable voltage drop should not exceed 7.2 volts (3% of 240V).

It's important to note that derating factors for conductors, such as those due to ambient temperature or multiple conductors in a raceway, are not included in this calculation for voltage drop. This means that the voltage drop should be calculated based solely on the length of the run and the load current without additional derating considerations.

Code reference

Refer to NEC Article 210.19(A)(1) for branch circuits and NEC Article 310 for conductor ampacity.

Field questions

What is the significance of the 3% voltage drop rule?
The 3% voltage drop rule is significant as it helps ensure that electrical devices operate efficiently and safely. Exceeding this limit can lead to performance issues and potential damage to equipment.
Why is derating excluded when calculating voltage drop?
Derating is excluded in voltage drop calculations to provide a straightforward assessment of the circuit's performance based solely on the load and distance, without complicating factors that may vary based on installation conditions.
How do I calculate the voltage drop for my circuit?
To calculate voltage drop, use the formula: Voltage Drop (V) = (2 × Length of the circuit in feet × Current in Amperes × Resistivity of the conductor) / 1000. For copper, the resistivity is approximately 10.4 ohms per mil foot.

Explore Related Engineering Calculations