40 amp copper run at 40 feet

Learn about the 3% NEC informational note for 240V copper branch circuits at 40A over 40 ft. Understand derating exclusions and ensure compliance with electrical codes.

Formula SSC-2026.1

K method · SSC-2026.1

Minimum size

8 AWG · 8.37 mm²

Single conductor set

Voltage drop

2.50 V

1.04% · end 237.5 V

Power loss

100 W

I²R at the operating current

Required ampacity

40.0 A

Each conductor 50 A

Material estimate

$235.20

3 conductors + EMT

Conductor weight

7.7 lb

3.5 kg · approximate insulated weight

Single-line and conductor gaugeLive scaled blueprint
MAIN PANELSingle-phase 240 VEMT · 40 ft · 8 AWG · 8.37 mm²Branch circuit40 ASelected gauge8 AWGaluminum8 AWGDrop 1.04%End 237.5 VLoss 100 W

Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.

Bill of materials and shopping list
ItemNetWasteOrderUnit priceLine totalSource Spec Material / Tool
copper 8 AWG · 8.37 mm²40 ft one waycuts excluded3 conductorsUSD$161.20Source Spec Material / Tool
EMT conduit40 ft—40 ftUSD$74.00Source Spec Material / Tool
40 A breaker2-pole—1Match the calculated load—Source Spec Material / Tool

Source links open a product search on the Amazon storefront for the selected currency. SiteSpecCalc may earn a commission. The link does not change the quantities above.

Copper versus aluminum at this run
MaterialMinimum sizemm²DropEnd voltageLoss
copper8 AWG · 8.37 mm²8.41.04%237.5 V100 W
aluminum8 AWG · 8.37 mm²8.41.71%235.9 V164 W
Same load at other one-way distances
DistanceMinimum sizeDropPercentEnd voltage
40 ft8 AWG · 8.37 mm²2.50 V1.04%237.5 V
65 ft8 AWG · 8.37 mm²4.06 V1.69%235.9 V
Show the deterministic formula

Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.

Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.

The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.

Engineering notes

The National Electrical Code (NEC) provides guidelines for the safe installation of electrical systems. One important aspect is the 3% voltage drop recommendation for branch circuits. For a 240V copper branch circuit carrying 40A over a distance of 40 feet, the NEC suggests that the voltage drop should not exceed 3% to ensure efficient operation and minimize energy loss.

It's important to note that derating factors, which may apply to certain conditions such as temperature or conduit fill, are excluded from this voltage drop calculation. This means that the 3% guideline is based on the circuit's nominal capacity without adjustments for these factors.

Code reference

Refer to NEC Article 210 for branch circuits and Article 310 for conductors.

Field questions

What is the significance of the 3% voltage drop recommendation?
The 3% voltage drop recommendation helps ensure that electrical devices receive adequate voltage for optimal performance, reducing the risk of overheating and energy loss.
Why is derating excluded from the 3% voltage drop calculation?
Derating is excluded to provide a clear guideline for voltage drop based solely on the circuit's nominal capacity, ensuring that installations remain efficient under standard conditions.
How do I calculate the voltage drop for my circuit?
To calculate voltage drop, you can use the formula: Voltage Drop (V) = (2 x Length of Circuit (ft) x Current (A) x Resistance of Conductor (Ω/ft)). Ensure that the result does not exceed 3% of the system voltage.