40 amp copper run at 80 feet

Learn about the 3% NEC informational note regarding voltage drop for 240V copper branch circuits at 40A over 80 ft. Understand derating exclusions and ensure compliance.

Formula SSC-2026.1

K method · SSC-2026.1

Minimum size

8 AWG · 8.37 mm²

Single conductor set

Voltage drop

5.00 V

2.08% · end 235.0 V

Power loss

200 W

I²R at the operating current

Required ampacity

40.0 A

Each conductor 50 A

Material estimate

$470.40

3 conductors + EMT

Conductor weight

15.4 lb

7.0 kg · approximate insulated weight

Single-line and conductor gaugeLive scaled blueprint
MAIN PANELSingle-phase 240 VEMT · 80 ft · 8 AWG · 8.37 mm²Branch circuit40 ASelected gauge8 AWGaluminum6 AWGDrop 2.08%End 235.0 VLoss 200 W

Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.

Bill of materials and shopping list
ItemNetWasteOrderUnit priceLine totalSource Spec Material / Tool
copper 8 AWG · 8.37 mm²80 ft one waycuts excluded3 conductorsUSD$322.40Source Spec Material / Tool
EMT conduit80 ft—80 ftUSD$148.00Source Spec Material / Tool
40 A breaker2-pole—1Match the calculated load—Source Spec Material / Tool

Source links open a product search on the Amazon storefront for the selected currency. SiteSpecCalc may earn a commission. The link does not change the quantities above.

Copper versus aluminum at this run
MaterialMinimum sizemm²DropEnd voltageLoss
copper8 AWG · 8.37 mm²8.42.08%235.0 V200 W
aluminum6 AWG · 13.3 mm²13.32.15%234.8 V207 W
Same load at other one-way distances
DistanceMinimum sizeDropPercentEnd voltage
80 ft8 AWG · 8.37 mm²5.00 V2.08%235.0 V
105 ft8 AWG · 8.37 mm²6.56 V2.73%233.4 V
Show the deterministic formula

Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.

Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.

The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.

Engineering notes

The National Electrical Code (NEC) provides guidelines for voltage drop in electrical systems to ensure efficiency and safety. For a 240V copper branch circuit carrying 40A over a distance of 80 feet, the NEC suggests that the voltage drop should not exceed 3% of the system voltage.

This means that for a 240V circuit, the maximum allowable voltage drop would be 7.2V (3% of 240V). It is important to note that derating factors are not included in this calculation, as the 3% guideline is based on the nominal voltage drop without considering additional derating due to temperature, conduit fill, or other factors.

Code reference

Refer to NEC Article 210 for branch circuits and NEC Article 310 for conductors.

Field questions

What is the significance of the 3% voltage drop rule?
The 3% voltage drop rule helps ensure that electrical systems operate efficiently and safely, reducing the risk of overheating and equipment malfunction.
Why is derating excluded from the 3% calculation?
Derating is excluded from the 3% calculation to provide a baseline for voltage drop that is independent of other factors, ensuring that the circuit can handle the load without additional complications.
How do I calculate the voltage drop for my circuit?
To calculate voltage drop, you can use the formula: Voltage Drop (V) = (2 * Length of Circuit (ft) * Current (A) * Resistance of Conductor (Ω/ft)). Ensure to use the correct resistance value for copper conductors.