Solar String Wire Size, 15A at 100 Feet

This is a DC-nameplate planning analog at 15 A continuous over 100 ft. It uses the same K method as an AC branch. It is not a PV source-circuit calculation under Article 690.

Formula SSC-2026.1

K method · SSC-2026.1

Minimum size

12 AWG · 3.31 mm²

Single conductor set

Voltage drop

5.93 V

2.47% · end 234.1 V

Power loss

89 W

I²R at the operating current

Required ampacity

18.8 A

Each conductor 20 A

Material estimate

$346.20

3 conductors + EMT

Conductor weight

6.9 lb

3.1 kg · approximate insulated weight

Single-line and conductor gaugeLive scaled blueprint
MAIN PANELSingle-phase 240 VEMT · 100 ft · 12 AWG · 3.31 mm²Solar string15 ASelected gauge12 AWGaluminum10 AWGDrop 2.47%End 234.1 VLoss 89 W

Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.

Bill of materials and shopping list
ItemNetWasteOrderUnit priceLine total
copper 12 AWG · 3.31 mm²100 ft one waycuts excluded3 conductorsUSD$161.20
EMT conduit100 ft—100 ftUSD$185.00
Copper versus aluminum at this run
MaterialMinimum sizemm²DropEnd voltageLoss
copper12 AWG · 3.31 mm²3.32.47%234.1 V89 W
aluminum10 AWG · 5.26 mm²5.32.55%233.9 V92 W
Same load at other one-way distances
DistanceMinimum sizeDropPercentEnd voltage
75 ft12 AWG · 3.31 mm²4.44 V1.85%235.6 V
100 ft12 AWG · 3.31 mm²5.93 V2.47%234.1 V
125 ft10 AWG · 5.26 mm²4.66 V1.94%235.3 V
Show the deterministic formula

Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.

Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.

The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.

Engineering notes

This is a DC-nameplate planning analog at 15 A continuous over 100 ft. It uses the same K method as an AC branch. It is not a PV source-circuit calculation under Article 690. The run is 100 ft one way at 15 A on 1ph-240. K is 12.9 for copper and 21.2 for aluminum. Ambient temperature, bundling, and rooftop adders are not applied.

Code reference

NEC 210.19(A) and 215.2(A) informational notes recommend 3 percent on a branch circuit and 5 percent total with the feeder. Ampacity follows the 75°C column of Table 310.16 plus the small-conductor limits. Confirm the adopted edition.

Field questions

What current is used for the 15 A voltage drop?
Voltage drop uses the operating amps. Ampacity uses 125 percent because the load is marked continuous.
Does this replace the equipment installation manual?
No. The nameplate, the breaker, and the adopted NEC edition still control. This page is the K-method size and the percent drop.
Can I switch copper and aluminum?
Yes. The conductor control and the comparison table both recompute size, drop, and the planning cost.