Solar String Wire Size, 20A at 150 Feet

Twenty amps continuous at 150 ft shows how a modest current still grows the conductor when the one-way distance is long.

Formula SSC-2026.1

K method · SSC-2026.1

Minimum size

8 AWG · 8.37 mm²

Single conductor set

Voltage drop

4.69 V

1.95% · end 235.3 V

Power loss

94 W

I²R at the operating current

Required ampacity

25.0 A

Each conductor 50 A

Material estimate

$882.00

3 conductors + EMT

Conductor weight

28.8 lb

13.1 kg · approximate insulated weight

Single-line and conductor gaugeLive scaled blueprint
MAIN PANELSingle-phase 240 VEMT · 150 ft · 8 AWG · 8.37 mm²Solar string20 ASelected gauge8 AWGaluminum6 AWGDrop 1.95%End 235.3 VLoss 94 W

Circle diameters track circular mils. The drawing is a schematic, not a conduit-fill layout.

Bill of materials and shopping list
ItemNetWasteOrderUnit priceLine total
copper 8 AWG · 8.37 mm²150 ft one waycuts excluded3 conductorsUSD$604.50
EMT conduit150 ft—150 ftUSD$277.50
Copper versus aluminum at this run
MaterialMinimum sizemm²DropEnd voltageLoss
copper8 AWG · 8.37 mm²8.41.95%235.3 V94 W
aluminum6 AWG · 13.3 mm²13.32.02%235.2 V97 W
Same load at other one-way distances
DistanceMinimum sizeDropPercentEnd voltage
125 ft10 AWG · 5.26 mm²6.21 V2.59%233.8 V
150 ft8 AWG · 8.37 mm²4.69 V1.95%235.3 V
175 ft8 AWG · 8.37 mm²5.47 V2.28%234.5 V
Show the deterministic formula

Single phase: Vdrop = 2 × K × I × D / cmil. Three phase: Vdrop = 1.732 × K × I × D / cmil. K is 12.9 for copper and 21.2 for aluminum. D is one-way feet.

Percent drop = Vdrop ÷ source voltage × 100. Green is 3% or less, amber is 3 to 5%, and red is over 5%. Power loss is I²R on the current-carrying conductors.

The smallest conductor that meets both the ampacity (125% when continuous) and the drop limit is selected. Ampacity does not include bundling or temperature correction.

Engineering notes

Twenty amps continuous at 150 ft shows how a modest current still grows the conductor when the one-way distance is long. The run is 150 ft one way at 20 A on 1ph-240. K is 12.9 for copper and 21.2 for aluminum. Ambient temperature, bundling, and rooftop adders are not applied.

Code reference

NEC 210.19(A) and 215.2(A) informational notes recommend 3 percent on a branch circuit and 5 percent total with the feeder. Ampacity follows the 75°C column of Table 310.16 plus the small-conductor limits. Confirm the adopted edition.

Field questions

What current is used for the 20 A voltage drop?
Voltage drop uses the operating amps. Ampacity uses 125 percent because the load is marked continuous.
Does this replace the equipment installation manual?
No. The nameplate, the breaker, and the adopted NEC edition still control. This page is the K-method size and the percent drop.
Can I switch copper and aluminum?
Yes. The conductor control and the comparison table both recompute size, drop, and the planning cost.